Nominal voltage
Built-in memory card slot, support microSD/SDHC/SDXC card (up to 256GB); manual recording/alarm recording kV
Rated tripping current
20000...31500 A
Highest operating voltage
40,5 kV
Rated current
630...2500 A
Normalized parameters of through short-circuit currents: electrodynamic resistance currents
51000...81000 A
Normalized parameters of through short-circuit currents: thermal resistance currents
20000...31500 A
Rated supply voltage for control circuits and auxiliary circuit elements
220 V
Rated current of control circuits of on/off solenoids not more than
1 A
Operating voltage range of control circuits (AC/DC) of the actuation solenoid
70–115 / 85–105% of U_nom %
Operating voltage range of the control circuits (AC/DC) of the trip solenoid
65–120 / 70–110% of U_nom %
Operating voltage range of control circuits (AC/DC) of the power spring cocking motor
85–110% of U_nom %
Mechanical life (number of cycles B-tp-O), not less than
10000 pcs
Switching life (number of cycles ?- tP-O) at rated tripping current, not less than
25 pcs
Service life before decommissioning, not less
30 year
Operating ambient air temperature range
from minus 25 to plus 40° °C
Resistance to seismic effects according to MSK-64 scale
9 points
Current type of control coil
alternating/direct
poles
the pole body is a molded structure made of dielectric materials. Inside the pole is a VDK. The pole's contact leads are connected to the corresponding VDK contacts.
drive
spring actuator, independent action, using mechanical energy of a pre-tensioned spring. The spring mechanism ensures the movement of the rods of the moving contacts with the required speed and stroke characteristics.
Degree of protection according to GOST 14254-96
IP4X
Control circuit current type
alternating/direct
Availability of built-in controls
yes
Type of climatic version according to GOST 15150-69
U